Solar PV Cable: H1Z2Z2-K, EN 50618 and IEC 62930
The DC side of a photovoltaic array is not an ordinary electrical installation. Cable runs in permanent sunlight, at up to 1.5 kV DC, on a circuit that cannot be switched off during daylight. This page sets out how PV cable is specified, what the designations actually mean, and how conductor size is chosen — the decisions that determine whether a string survives twenty-five years in the field.
Why PV cable is a separate product
A PV array puts a cable in conditions that no building cable standard was written for. Four of them matter more than the rest.
1.5 kV DC, not 400 V AC
Utility-scale strings now operate at 1500 V DC, and IEC 62930 and EN 50618 set the reference rating at 1.5 kV DC. Standard 0.6/1 kV building cable is neither rated nor tested for that. Direct current also arcs differently from alternating current: it has no natural zero crossing, so a connector or cable fault that would self-extinguish on AC can sustain.
Permanent UV and ozone exposure
Most DC cable is clipped to the mounting structure in direct sunlight for the life of the plant. EN 50618 therefore specifies cross-linked halogen-free polyolefin insulation and sheath rather than PVC, and includes ozone and weathering tests. This is the single most common reason cheap non-PV cable fails early in the field.
The circuit stays live
A PV array cannot be switched off at the source. As long as there is light there is voltage on the string, so cable and connector work on the DC side is live work by definition. Cable that keeps its insulation properties and its joint resistance is what makes that tolerable.
Wide temperature cycling, every day
A conductor in full sun can sit far above ambient while carrying current, then cool overnight. The cycling repeats every day for decades. The class 5 fine-strand conductor and the cross-linked insulation are chosen to tolerate that movement without hardening or cracking.
H1Z2Z2-K and PV1-F: what the designations mean
Two designations appear on almost every PV cable datasheet. They come from different documents and should not be treated as synonyms.
| Aspect | H1Z2Z2-K | PV1-F |
|---|---|---|
| Source document | EN 50618 (European standard for photovoltaic system cables) | TÜV Rheinland specification 2 PfG 1169 |
| Rated voltage | 1.0/1.0 kV AC, 1.5 kV DC | 0.6/1.0 kV AC, 1.8 kV DC |
| Max. conductor temperature | 90 °C continuous, 120 °C for 20,000 h | 90 °C continuous |
| Conductor | Tinned copper, class 5 to EN 60228 | Tinned copper, fine strand |
| Insulation and sheath | Cross-linked halogen-free polyolefin (XLPO) | Cross-linked halogen-free polyolefin |
| Where it is specified | European and international projects citing EN 50618 or IEC 62930 | Projects where the specification names TÜV 2 PfG 1169 |
Construction and materials
Every item below exists for a reason that shows up in the field. This is the specification of the Treasol H1Z2Z2-K range.
| Property | Value |
|---|---|
| Type designation | H1Z2Z2-K to EN 50618; PV1-F to TÜV 2 PfG 1169 also available |
| Rated voltage | 1.0/1.0 kV AC, 1.5 kV DC |
| Max. system voltage | 1500 V DC |
| Conductor | Tinned copper, class 5 to EN 60228 — flexible, and corrosion resistant at the strands |
| Insulation | Cross-linked halogen-free polyolefin |
| Sheath | Cross-linked halogen-free polyolefin, low smoke |
| Service temperature | −40 °C to +90 °C |
| Max. conductor temperature | +120 °C for 20,000 h |
| Flame retardant | EN 60332-1-2 |
| Halogen free | EN 60754-1 / EN 60754-2 |
| Ozone resistance | EN 60811-2-1 |
| Cross section | 2.5 / 4.0 / 6.0 / 10 / 16 mm² |
| Colours | Red and black |
Ozone resistance is worth singling out. Ozone is produced around electrical equipment and in strong sunlight, and it attacks the double bonds in ordinary rubber and some polyolefin compounds, causing surface cracking that then propagates under bending. EN 60811-2-1 is the test that separates a genuine PV compound from a cable that merely looks black and flexible on delivery.
Choosing the cross section
Two requirements decide the conductor size, and on real projects the second one usually wins.
| Cross section | Typical use | What decides it |
|---|---|---|
| 2.5 mm² | Short module-to-module jumpers, low-current runs | Ampacity is rarely the limit; used where runs are short and mechanical handling favours a smaller cable |
| 4 mm² | Common for residential and small commercial strings | Frequently the minimum that satisfies voltage drop on a typical roof run |
| 6 mm² | The default for most commercial and utility-scale string wiring | The usual balance between voltage drop, ampacity and handling |
| 10 mm² | Long string home runs, larger string currents | Chosen when voltage drop on a long run exceeds the allowance at 6 mm² |
| 16 mm² | Long DC feeders, combiner-box to inverter runs | Voltage drop and, at higher currents, ampacity together |
Derating and voltage drop
A cable rating in a table is measured under stated conditions. Site conditions are not those conditions.
Voltage drop is a round trip
Current flows out along one conductor and back along the other, so the drop is twice the one-way figure. For a 6 mm² tinned copper conductor the resistance is roughly 3.39 Ω/km at 20 °C. At 10 A over 100 m of a 6 mm² string the drop is on the order of 6.8 V — a small fraction of a 1500 V system, which is why drop only becomes decisive on long runs or low-voltage strings.
The 2 percent design allowance
A common specification limit is about 2 percent total DC voltage drop between the array and the inverter. It is a design allowance rather than a standard requirement, and the project specification governs. The practical consequence is that the allowance is spent across the whole DC path, not per cable run, so leaving margin in the string cable matters.
Why ambient temperature derates
The conductor is rated to 90 °C continuous. If the surrounding air is already at 70 °C inside a rooftop conduit, the permissible temperature rise — and therefore the current — is smaller than the free-air table suggests. The same applies where several cables are bundled or run in a common conduit, because they heat each other.
Read the conditions, not the number
A current rating is only meaningful with its reference conditions attached: ambient temperature, installation method, number of loaded conductors. Two datasheets quoting different figures for the same cross section are usually quoting different conditions, not different quality.
Standards and compliance
Which document governs depends on where the array is built and what the project specification names.
| Document | What it covers |
|---|---|
| EN 50618 | Electric cables for photovoltaic systems. European standard; source of the H1Z2Z2-K designation. The reference document for PV DC cable in European projects. |
| IEC 62930 | Electric cables for photovoltaic systems. The international counterpart, describing the same class of cross-linked halogen-free PV DC cable. A cable made to IEC 62930 may be designated H1Z2Z2-K where it also meets EN 50618. |
| UL 4703 | North American standard for photovoltaic wire. Applies to US and Canadian projects in place of, or alongside, the EN and IEC documents. |
| EN 60228 | Conductors of insulated cables. Defines class 5 flexible stranding, which is what makes PV cable handleable in the field. |
| IEC 62548-1 / IEC 60364-7-712 | Installation standards for PV arrays and low-voltage PV power systems. They govern how the cable is installed, not how it is made. |
Cable standards and connector standards are separate documents covering separate products. If you are qualifying a complete string assembly, the connector side is covered in the PV connector and cable standards reference, and the certification side in the PV connector certification hub.
In-depth guides
Each of these goes deeper on one part of the decision above. This page is the index; they are the detail.
Frequently asked questions about solar PV cable
The questions engineers and buyers ask most often. Product-specific questions are answered in our product FAQ.
Specify PV Cable for Your Project
Tell us the string current, the one-way run length, the system voltage and the standard your project references. We will come back with the cross section that satisfies both the voltage-drop and ampacity checks, together with the cable data you need for the submittal.
What you can receive:
- Datasheet with the full EN 50618 construction and ratings
- Standard the cable is manufactured and tested to
- Recommended cross section for your run and current
- Mating connector recommendation for the same cable size
- MOQ, lead time and OEM options
Contact the PV cable team
Send us the parameters above and our engineering team will confirm the right cable and the connector that matches it. We normally respond within 24 hours.