Professional PV Connector Manufacturer
TÜV Rheinland · UL · CE · RoHS — Product-Specific Certification & Compliance | info@treasol.com

A fuse connector puts string overcurrent protection directly on the DC cable, in a weatherproof housing that mates with the standard PV connector interface. It replaces a separate fuse holder and its enclosure, which removes two connection points and the extra cable length between them — both common sources of voltage drop and water ingress on a rooftop array.

The range covers both common fuse sizes. F4C-200-1085 and F4C-201-1085 take the 10.3 × 85 mm fuse and are rated 1500 V with 1 to 30 A fuses; F4C-212-1038 takes the compact 10.3 × 38 mm fuse at 1000 V/1100 V TÜV. All three are IP68 in the mated condition with contact resistance below 0.5 mΩ.

Showing 3 products in this category

Specification comparison

Technical specification comparison for products in this category
Model Rated voltage Rated current Protection Contact resistance Conductor size
F4C-200-1085 Solar Fuse Connector 1500 V (TUV) 1500 V (UL) 1-30 A IP 68 <0.5 mΩ —
F4C-212-1038 Solar Fuse Connector 1000 V/1100 V (TUV) 600 V (UL) 1-30 A IP 68 <0.5 mΩ —
F4C-201-1085 Solar Fuse Connector 1500 V (TUV) 1500 V (UL) 1-30 A IP 68 <0.5 mΩ —

Values are the mated-pair ratings from our published datasheets. Where a field is blank, that variant does not specify it — ask us and we will confirm against the drawing for your configuration.

Frequently asked questions

How do I size the fuse for a string?

The fuse must carry the string current continuously and still open on a fault. Work from the module Isc: the usual rule is to rate at 1.25× Isc and stay within the module series-fuse rating, then check that the fuse holds at the highest expected ambient. Oversizing for temperature is the usual mistake — it delays clearing on a genuine fault.

Which fuse size should I choose, 10.3 × 85 mm or 10.3 × 38 mm?

The physical size follows the voltage and breaking capacity you need. The 85 mm body carries the 1500 V rating; the compact 38 mm body is rated 1000 V/1100 V. If the array runs at 1500 V DC, use the 85 mm version.

Does the fuse connector meet the connector standard as well?

The mated interface follows the same PV connector construction as the rest of the range, and the fuse element is a separate certified component. Check both: the connector standard covers the housing and contact, while the fuse has its own rating for voltage, current and breaking capacity.

Need a Custom Solution or Bulk Quote?

Our engineering team can help with technical specifications, OEM requirements and competitive pricing for your project needs.

Contact Us Today
CONTACT
WhatsApp Email